California Instruments 801RP Series Dokumentacja Strona 91

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 126
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 90
CALibrate:MEASure:POWer[:FSCale] <NRf>
This command affects the calibration of the power measurement at full scale.
Command Syntax CALibrate:MEASure:POWer[:FSCale] <NRf>
Parameters <NRf> (value range -127 to +127)
Examples CAL:MEAS:POW 78
Query Syntax CALibrate:MEASure:POWer?
Returned Parameters <NR1> (value range -127 to +127)
Related Commands CALibrate:MEASure:CURRent
CALibrate:MEASure:POWer:ZERO <NRf>
This command affects the calibration of the power measurement zero offset.
Command Syntax CALibrate:MEASure:POWer:ZERO <NRf>
Parameters <NRf> (value range -127 to +127)
Examples CAL:MEAS:POW:ZERO -5
Query Syntax CALibrate:MEASure:POWer:ZERO?
Returned Parameters <NR1> (value range -127 to +127)
Related Commands CALibrate:MEASure:POWer
CALibrate:MEASure:VOLTage[:FSCale] <NRf>
This command affects the calibration of the rms voltage measurement at full scale.
Command Syntax CALibrate:MEASure:VOLTage[:FSCale] <NRf>
Parameters <NRf> (value range -127 to +127)
Examples CAL:MEAS:VOLT 56
Query Syntax CALibrate:MEASure:VOLTage?
Returned Parameters <NR1> (value range -127 to +127)
Related Commands CALibrate:MEASure:CURRent
CALibrate:MEASure:VOLTage:ZERO <NRf>
This command affects the calibration of the rms voltage measurement zero offset.
Command Syntax CALibrate:MEASure:VOLTage:ZERO <NRf>
Parameters <NRf> (value range -127 to +127)
Examples CAL:MEAS:VOLT:ZERO +4
Query Syntax CALibrate:MEASure:VOLTage:ZERO?
Returned Parameters <NR1> (value range -127 to +127)
Related Commands CALibrate:MEASure:VOLTage